item | Parameters & Options |
Input voltage waveform | Sine wave (AC or Generator) |
Rated input voltage | 230Vac |
Low voltage breakpoint | 184Vac±4% |
Low pressure recovery point | 194Vac ±4% |
Hv breakpoint | 253Vac±4% |
High voltage recovery point | 243Vac±4% |
Maximum input voltage | 270Vac rms |
Rated input frequency | 50Hz/ 60Hz (automatic detection) |
Low voltage recovery point frequency | 58+0.3Hz (60Hz);48+0.3Hz(50Hz); |
Low voltage breakpoint frequency | 57+0.3Hz(60Hz);47+0.3Hz (50Hz); |
High voltage recovery point frequency | 64+0.3Hz (60Hz);54+0.3Hz (50Hz); |
High - voltage breakpoint frequency | 65+0.3Hz (60Hz);55+0.3Hz (50Hz); |
Output voltage waveform | Consistent with the input voltage waveform |
Overload protection | Circuit breaker starts |
Short circuit protection | Circuit breaker starts |
Power efficiency | >95% |
Convert current | 30Aac |
AC to DC conversion time | 10ms |
DC to AC conversion time | 10ms |
Bypass switching current | Yes |
Bypass maximum load current | 30Aac |
Output voltage waveform | Pure sine wave |
Rated output capacity (VA) | 5000 |
Rated output power (W) | 5000 |
Power factor | 0.9-1.0 |
Rated output voltage (V) | 230Vac |
Rated output frequency (Hz) | 50Hz ± 0.3Hz |
Automatic tracking frequency (Hz) | 50Hz @48-54Hz 60Hz @58-64Hz |
Output voltage range | ±10% rms |
effectiveness | >85% |
Overload protection | (110% (125% Load> 150% ± 10%: Disconnect the output voltage after 20 seconds |
Peak capacity (10s) | 12000VA |
Motor starting ability | 2 HP |
Short circuit protection | Current limit (power off after 10s) |
Circuit breaker specifications | 30A |
Rated DC input voltage | 48Vdc |
Minimum DC voltage | 40Vdc |
Undervoltage warning | 42Vdc ± 0.3Vdc |
DC input voltage is too low | 40Vdc ± 0.3Vdc |
Input over-voltage warning and power failure | 64Vdc ± 0.3Vdc |
Input overvoltage recovery | 62Vdc± 0.3Vdc |
Power-saving mode to enter the conditions | Load ≦ 25W Enter power saving mode, load> 25W to enter normal model |